General |
  |
Codes of Practice |
  |
Guidance Notes / Guidelines |
| Code |
Description |
Demerit Point |
| 1. |
The following information for the work on locating the underground cable missing in the report :
- location; or
- date; or
- time; or
- name of competent person; or
- approval number of competent person; or
- name of contractor
|
1 |
| 2. |
The following information for the cable locating device used for the detection is missing in the report :
- brand name; or
- model number; or
- serial number; or
- calibration record
|
1 |
| 3. |
Cable information as shown in the report is not accurate because :
- The deviation in cable alignment is more than 25% of the actual cable depth; or
- The deviation in cable depth is more than 25% of the actual cable depth; or
- There is deviation in cable quantity
|
2 |
| 4. |
The following underground cable information is missing in the report :
- alignment; or
- reference point; or
- depth profile; or
- cable quantity; or
- voltage level
|
2 |
| 5. |
Fail to mark the cable alignment or depth on site. |
2 |
| 6. |
Plan of the underground cable obtained from the electricity supplier is not used. |
3 |
| 7. |
The report details such as alignment, depth, etc. are not explained to the contractors, supervisors or workers before carrying out the excavation work. |
3 |
| 8. |
Passive detection to locate cable alignment is not carried out. |
3 |
| 9. |
Active detection (such as toroidal injection with a signal clamp) to identify cable position is not carried out. |
3 |
| 10. |
Fail to identify or record the existence of cable. |
3 |
| 11. |
Produce incomplete or inaccurate report leading to electrical accident which causes injury. |
4 |
| 12. |
Produce incomplete or inaccurate report leading to interruption of supply to consumer or interruption to circuit by damaging cable of 11kV or below. |
4 |
| 13. |
Produce incomplete or inaccurate report leading to electrical accident which causes death. |
6 |
| 14. |
Produce incomplete or inaccurate report leading to interruption of supply to consumer or interruption to circuit by damaging cable of above 11kV. |
6 |