Witty Bear is ready, click to connect KnowBot Chatbot
Skip to main content

Frequently Asked Questions

Electrical Installation

Show all answers

  1. Pursuant to Schedule 3 of the Buildings Energy Efficiency Ordinance, the work is regarded as a "Major Retrofitting Works" if the work involves addition of a complete electrical circuit at rating of 400A or above. Based on Table 10.1 of the latest edition of the Building Energy Code, relevant clauses of the BEC regarding power distribution losses, total power factor, total harmonic distortion, balancing of single -phase loads, metering & monitoring facilities should be followed. The responsible person of the works should obtain the Form of Compliance from a Registered Energy Assessor within 2 months after completion of the works.

    Back to top

  2. The requirement on the provision of metering and monitoring facilities had already been stipulated in BEC 2012. In the issuance of BEC 2012 (Rev.1) and BEC 2015, such requirement had not been further amended or tightened. Therefore, the above mentioned TG Figure is also applicable to the BEC 2012 and BEC 2012 (Rev. 1).

    Back to top

  3. During the stage two declaration submission, if the power factor and harmonic corrective devices are supplied and installed by future tenant, the document proof such as tenancy agreement should be submitted also showing that the provision would be taken up by the tenant.

    Back to top

  4. Guidance on the compliance with motor sizing requirement is shown in the latest edition of the TG-BEC. Further examples and elaboration have also been given in TG-BEC covering the same. The 125% is NOT a multiplier being imposed to the anticipated system load but solely a criterion to avoid motor oversizing. For example, having the anticipated system load at 10 kW, the suitable standard motor rating shall be the 11kW. Then, having 11 kW/ 10 kW = 110% complies with the “not exceeding 125%” criterion.

    Back to top

Please download Acrobat Reader to view the PDF files.